Plumbers are Required to make Applications for Water Meters
for new service lines at the Utility Building or by calling 605-697-8408. We appreciate at least two days’ notice for installation of new meters.
The following lead-free backflow preventers will be allowed (or approved equal):
- Zurn Wilkins – Model 700XL Lead-Free
- Watts – Series 7 Dual Check Valves
The meter yoke shall be a copper male-by-female swivel jointed meter yoke with a:
- 7 ½” lay length for ¾” meters
- 11” lay length for 1” meters
No solder joints will be allowed. All meter yokes brass or bronze parts, no lead brass.
The following meter yokes will be allowed (or approved equal):
- A.Y. McDonald Manufacturing Company
- Ford Meter Box Company Inc.